Citation ID |
01001 |
Citaton Type |
Serious |
Standard Cited |
19100037 A03 |
Issuance Date |
2014-05-21 |
Current Penalty |
1400.0 |
Initial Penalty |
2800.0 |
Final Order |
2014-06-13 |
Nr Instances |
1 |
Nr Exposed |
3 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.37(a)(3): Exit route(s) were not kept free and unobstructed: ESTABLISHMENT: The emergency exit door was obstructed by a table and a steel ornament. |
|
Citation ID |
01002A |
Citaton Type |
Serious |
Standard Cited |
19100132 D02 |
Issuance Date |
2014-05-21 |
Abatement Due Date |
2014-06-17 |
Current Penalty |
1400.0 |
Initial Penalty |
2800.0 |
Final Order |
2014-06-13 |
Nr Instances |
1 |
Nr Exposed |
3 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.132(d)(2): The employer did not verify, through a written certification, the identity of the workplace evaluated, the person certifying that the evaluation had been performed, and the date the hazard assessment was done: ESTABLISHMENT: The employer did not verify through written certification, the Workplace Hazard Assessment plan. |
|
Citation ID |
01002B |
Citaton Type |
Serious |
Standard Cited |
19100135 A01 |
Issuance Date |
2014-05-21 |
Abatement Due Date |
2014-06-03 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2014-06-13 |
Nr Instances |
1 |
Nr Exposed |
3 |
Gravity |
1 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.135(a)(1): The employer did not ensure that each affected employee wear a protective helmet when working in areas where there is a potential for injury to the head from falling objects: ESTABLISHMENT: The employees operating an overhead crane to hoist steel and equipment were not provided with protective hard hats. |
|
Citation ID |
01003 |
Citaton Type |
Serious |
Standard Cited |
19100178 P01 |
Issuance Date |
2014-05-21 |
Abatement Due Date |
2014-06-17 |
Current Penalty |
1400.0 |
Initial Penalty |
2800.0 |
Final Order |
2014-06-13 |
Nr Instances |
1 |
Nr Exposed |
1 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.178(p)(1): Powered industrial truck(s) found to be in need of repair, defective, or in any way unsafe had not been taken out of service until restored to safe operating condition(s): ESTABLISHMENT: The Mitsubishi forklift truck used by the forklift operator with a broken front light and severely torn seat and had not been removed from service until repaired. |
|
Citation ID |
01004 |
Citaton Type |
Serious |
Standard Cited |
19100253 B04 III |
Issuance Date |
2014-05-21 |
Current Penalty |
1050.0 |
Initial Penalty |
2100.0 |
Final Order |
2014-06-13 |
Nr Instances |
1 |
Nr Exposed |
3 |
Gravity |
1 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.253(b)(4)(iii): Oxygen cylinders in storage were not separated from fuel-gas cylinders or combustible materials (especially oil or grease), a minimum distance of 20 feet (6.1 m) or by a noncombustible barrier at least 5 feet (1.5 m) high having a fire-resistance rating of at least one half hour: ESTABLISHMENT: A compressed gas cylinder of oxygen was stored on a cart with a compressed gas cylinder of acetylene. |
|
Citation ID |
01005 |
Citaton Type |
Serious |
Standard Cited |
19100254 D09 III |
Issuance Date |
2014-05-21 |
Abatement Due Date |
2014-06-03 |
Current Penalty |
1750.0 |
Initial Penalty |
3500.0 |
Final Order |
2014-06-13 |
Nr Instances |
1 |
Nr Exposed |
3 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.254(d)(9)(iii): Cables with damaged insulation or exposed bare conductors were not replaced: ESTABLISHMENT: The insulation of the cables used for the Airco "Tig" Heliwelder were damaged and had exposed bare conductors. |
|
Citation ID |
01006A |
Citaton Type |
Serious |
Standard Cited |
19100303 B02 |
Issuance Date |
2014-05-21 |
Current Penalty |
1750.0 |
Initial Penalty |
3500.0 |
Final Order |
2014-06-13 |
Nr Instances |
1 |
Nr Exposed |
1 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: ESTABLISHMENT: The electrical metal outlet box used to power a Hobart welding machine was not securely mounted as required and was subject to physical damage. |
|
Citation ID |
01006B |
Citaton Type |
Serious |
Standard Cited |
19100305 B01 |
Issuance Date |
2014-05-21 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2014-06-13 |
Nr Instances |
1 |
Nr Exposed |
1 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.305(b)(1): Unused openings in boxes, cabinets, or fittings were not effectively closed: ESTABLISHMENT: The electrical metal outlet box used to power a Hobart welding machine had an unused opening. |
|
Citation ID |
01007A |
Citaton Type |
Serious |
Standard Cited |
19100304 G05 |
Issuance Date |
2014-05-21 |
Abatement Due Date |
2014-06-03 |
Current Penalty |
1750.0 |
Initial Penalty |
3500.0 |
Final Order |
2014-06-13 |
Nr Instances |
1 |
Nr Exposed |
2 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective: ESTABLISHMENT: The attachment plug of the orange/black flexible cord used to power a P&H welder machine was missing a grounding pin. |
|
Citation ID |
01007B |
Citaton Type |
Serious |
Standard Cited |
19100305 G02 II |
Issuance Date |
2014-05-21 |
Abatement Due Date |
2014-06-03 |
Current Penalty |
0.0 |
Initial Penalty |
3500.0 |
Final Order |
2014-06-13 |
Nr Instances |
1 |
Nr Exposed |
3 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.305(g)(2)(ii): Hard-service cord and junior hard-service cord No. 14 and larger were repaired by splicing, which did not retain the insulation, outer sheath properties, and usage characteristics of the cord that was spliced:Note: Hard service flexible cords No. 12 or larger may be spliced if the splice retains the insulation, outer sheath properties, and usage characteristics of the cord being spliced. ESTABLISHMENT: The orange/black flexible cord used to power a P&H welder machine was repaired by splicing which did not retain the insulation, outer sheath properties, and usage characteristics of the cord. |
|
Citation ID |
01009 |
Citaton Type |
Serious |
Standard Cited |
19100305 G02 III |
Issuance Date |
2014-05-21 |
Abatement Due Date |
2014-06-03 |
Current Penalty |
1750.0 |
Initial Penalty |
3500.0 |
Final Order |
2014-06-13 |
Nr Instances |
1 |
Nr Exposed |
1 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.305(g)(2)(iii): Flexible cords were not connected to devices and fittings so that tension would not be transmitted to joints or terminal screws: ESTABLISHMENT: The outer insulation was pulled away exposing the insulated conductors at both the attachment point to Enco Band saw and at the attachment to the plug. |
|
Citation ID |
02001 |
Citaton Type |
Other |
Standard Cited |
19040032 B03 |
Issuance Date |
2014-05-21 |
Abatement Due Date |
2014-06-17 |
Current Penalty |
500.0 |
Initial Penalty |
1000.0 |
Final Order |
2014-06-13 |
Nr Instances |
1 |
Nr Exposed |
3 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1904.32(b)(3): The Summary of Work Related Injuries and Illnesses (OSHA Form 300A or equivalent) was not properly certified: ESTABLISHMENT: The OSHA 300A Summary form for 2013 was not signed and certified by a company executive. |
|
Citation ID |
02002 |
Citaton Type |
Other |
Standard Cited |
19100101 B |
Issuance Date |
2014-05-21 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2014-06-13 |
Nr Instances |
1 |
Nr Exposed |
3 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.101(b): The in-plant handling, storage, and utilization of all compressed gases in cylinders, portable tanks, rail tankcars, or motor vehicle cargo tanks were not in accordance with Compressed Gas Association Pamphlet P-1-1965, which is incorporated by reference as specified in CFR 1910.6: ESTABLISHMENT: An Argon compressed gas cylinder in storage was not equipped with a valve cap. |
|