Inspection Type |
Planned
|
Scope |
Partial
|
Safety/Health |
Health
|
Close Conference |
2015-07-14
|
Emphasis |
L: EISAOF, L: R1NOISE, N: CHEMNEP, P: CHEMNEP
|
Case Closed |
2015-10-08
|
Violation Items
Citation ID |
01001 |
Citaton Type |
Other |
Standard Cited |
19100119 E03 VII |
Issuance Date |
2015-07-20 |
Abatement Due Date |
2015-10-03 |
Current Penalty |
4250.0 |
Initial Penalty |
4250.0 |
Final Order |
2015-08-04 |
Nr Instances |
1 |
Nr Exposed |
40 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.119(e)(3)(vii): The process hazard analysis did not address a qualitative evaluation of a range of the possible safety and health effects of failure of controls on employees in the workplace: Facility: On, or about, June 13, 2014, the RCPHA for the covered process, dated January 31, 2014, did not include a qualitative evaluation of a range of the possible safety and health effects of failure of controls on employees in the workplace including, but not limited to, Scenario AP-1.01.361 and Scenario AP-1.01.263. |
|
Citation ID |
01003A |
Citaton Type |
Serious |
Standard Cited |
19100305 G01 IV A |
Issuance Date |
2015-07-20 |
Current Penalty |
4250.0 |
Initial Penalty |
4250.0 |
Final Order |
2015-08-04 |
Nr Instances |
1 |
Nr Exposed |
20 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: E-Train - On, or about, February 12, 2015, flexible cord was used in lieu of permanent wiring: The electric heat tracing tape on the V16 Vacuum Flush tank was energized by an orange extension cord. |
|
Citation ID |
01003B |
Citaton Type |
Serious |
Standard Cited |
19100305 G01 IV C |
Issuance Date |
2015-07-20 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2015-08-04 |
Nr Instances |
1 |
Nr Exposed |
20 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.305(g)(1)(iv)(C): Flexible cables were run through doorways, windows, or similar openings; E-Train - On, or about, February 12, 2015, an orange extension cord, used to energize the electric heat tracing tape on the V16 vacuum flush tank was run through a doorway. |
|
Citation ID |
01003C |
Citaton Type |
Serious |
Standard Cited |
19100305 G01 IV D |
Issuance Date |
2015-07-20 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2015-08-04 |
Nr Instances |
1 |
Nr Exposed |
20 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.305(g)(1)(iv)(D): Flexible cords were attached to building surfaces: E-Train - On, or about, February 12, 2015, an orange extension cord, used to energize the electric heat tracing tape on the V16 vacuum flush tank was strung over facility piping. |
|
Citation ID |
01003D |
Citaton Type |
Serious |
Standard Cited |
19100305 G01 I |
Issuance Date |
2015-07-20 |
Abatement Due Date |
2015-09-03 |
Current Penalty |
0.0 |
Initial Penalty |
4250.0 |
Final Order |
2015-08-04 |
Nr Instances |
1 |
Nr Exposed |
26 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.305(g)(1)(i): Flexible cords and cables were not approved for conditions of use and location: E-Train - On, or about, February 12, 2015, an orange extension cord used to energize the electric heat tracing tape on the exterior located V16 vacuum flush tank was not approved for use in a Class I, Division II electrical area or for outdoor use. |
|
|