Inspection Type |
Complaint
|
Scope |
Partial
|
Safety/Health |
Safety
|
Close Conference |
2023-12-05
|
Case Closed |
2024-03-01
|
Related Activity
Type |
Complaint |
Activity Nr |
2084045 |
Safety |
Yes |
|
Violation Items
Citation ID |
01001 |
Citaton Type |
Serious |
Standard Cited |
19100036 B01 |
Issuance Date |
2023-12-05 |
Abatement Due Date |
2024-03-01 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2024-01-04 |
Nr Instances |
1 |
Nr Exposed |
3 |
Gravity |
1 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.36(b)(1): At least two exit routes were not available to permit prompt evacuation of employees during an emergency: Basement Level: On, or about, October 16, 2023, a sufficient number of exits had not been provided from the work area. A Datron CNC machine was located at the lower landing of the interior stairs that used Reagent Alcohol 200 proof, a Category 2 flammable liquid with a flashpoint of 33.2�, F, as coolant. Dye was coated onto wooden parts at a dip coating workstation and the parts were air dried in the workspace. The Dye used was Dye #37, a Category 2 flammable liquid with a flashpoint of -4�, F. At the time of the inspection, a single means of egress from the workspace was provided using an interior staircase to the street level of the building. In accordance with the National Fire Protection Association (NFPA) Standard 101, Life Safety Code, two means of egress are required from the basement level due to the size of the work area and presence of high hazard contents and processes involving the use of flammable liquids. Abatement Note: The overhead door provided on the exterior wall does not meet the requirements of an exit door per 29 CFR 1910.36(e). |
|
Citation ID |
01002A |
Citaton Type |
Serious |
Standard Cited |
19100106 D02 III |
Issuance Date |
2023-12-05 |
Abatement Due Date |
2024-01-24 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2024-01-04 |
Nr Instances |
1 |
Nr Exposed |
3 |
Related Event Code (REC) |
Complaint |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.106(d)(2)(iii): Flammable or combustible liquid containers were not in accordance with Table H12: Basement Production Area: On, or about, October 16, 2023, Reagent Alcohol, was transferred into and stored in a two-gallon plastic jug that was used to feed the solvent into the coolant system on the Datron M35 CNC milling machine. 29 CFR 1910.103 Table H-12 limits the size of a plastic container to 1 quart when storing a Category 2 flammable liquid. Reagent Alcohol 200 proof is a Category 2 flammable liquid with a flashpoint of 33.2�, F. |
|
Citation ID |
01002B |
Citaton Type |
Serious |
Standard Cited |
19100106 E06 I |
Issuance Date |
2023-12-05 |
Abatement Due Date |
2024-03-01 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2024-01-04 |
Nr Instances |
2 |
Nr Exposed |
3 |
Related Event Code (REC) |
Complaint |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.106(e)(6)(i): Adequate precautions were not taken to prevent the ignition of flammable vapors: Basement Production Area: On, or about, October 16, 2023, Reagent Alcohol, a Category 2 flammable liquid with a flashpoint of 33.2�, F was used in the CNC machining process: A. A fifty-five gallon drum of Reagent Alcohol was not grounded. The barrel was sitting on a piece of plywood and the Reagent Alcohol was dispensed into a secondary container to be used at the Datron M35 CNC machine. B. A two-gallon plastic container used to dispense Reagent Alcohol 200 proof into the Datron CNC Machine was not grounded. |
|
Citation ID |
01002C |
Citaton Type |
Serious |
Standard Cited |
19100106 E06 II |
Issuance Date |
2023-12-05 |
Abatement Due Date |
2024-03-01 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2024-01-04 |
Nr Instances |
2 |
Nr Exposed |
3 |
Related Event Code (REC) |
Complaint |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.106(e)(6)(ii): Category 1 or 2 flammable liquids, or Category 3 flammable liquids with a flashpoint below 100 �F (37.8 �C), were dispensed into containers without the nozzle and container being electrically interconnected: Basement Production Area: On, or about, October 16, 2023, Reagent Alcohol 200 proof, a Category 2 flammable liquid with a flashpoint on 33.2�, F was used in the CNC machining process: A. A bonding wire was not used when the Reagent Alcohol was dispensed into a two-gallon secondary container. B. A bonding wire was not used when the Reagent Alcohol was transferred into the coolant system on the Datron M35 CNC milling machine. |
|
Citation ID |
01003A |
Citaton Type |
Serious |
Standard Cited |
19100125 A |
Issuance Date |
2023-12-05 |
Abatement Due Date |
2024-01-24 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2024-01-04 |
Nr Instances |
1 |
Nr Exposed |
3 |
Related Event Code (REC) |
Complaint |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.125(a): Dip tank was not made of noncombustible material: Downstairs, Dyeing Area: On, or about, October 16, 2023, an eight-gallon plastic storage container was used as a dip tank to coat wooden parts with Dye #37, a Category 2 flammable liquid with a flashpoint of -4�, F. |
|
Citation ID |
01003B |
Citaton Type |
Serious |
Standard Cited |
19100125 E01 I |
Issuance Date |
2023-12-05 |
Abatement Due Date |
2024-03-01 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2024-01-04 |
Nr Instances |
1 |
Nr Exposed |
3 |
Related Event Code (REC) |
Complaint |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.125(e)(1)(i): All electrical wiring and equipment in each vapor area and any adjacent area did not conform to the applicable hazardous (classified)-area requirements of subpart S of this part (except as specifically permitted in paragraph (g): Ref. 29 CFR 1910.307(c) Downstairs, Dyeing Area: On, or about, October 16, 2023, a standard duty box fan was used to exhaust vapors generated when parts were dipped and stacked to dry on the work counter. Parts were dyed with Dye #37, a Category 2 flammable liquid with a flashpoint of -4�, F. |
|
Citation ID |
01003C |
Citaton Type |
Serious |
Standard Cited |
19100125 E02 |
Issuance Date |
2023-12-05 |
Abatement Due Date |
2024-03-01 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2024-01-04 |
Nr Instances |
1 |
Nr Exposed |
3 |
Related Event Code (REC) |
Complaint |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.125(e)(2): Portable container(s) used to add liquid to the tank was not electrically bonded to the dip tank and was not positively grounded to prevent static electrical sparks or arcs: Downstairs, Dyeing Area: On, or about, October 16, 2023, containers of Dye #37, a Category 2 flammable liquid with a flashpoint of -4�, F were grounded. Also, containers of Dye #37 were not bonded during transfers from one container to another. |
|
Citation ID |
01003D |
Citaton Type |
Serious |
Standard Cited |
19100125 E04 I |
Issuance Date |
2023-12-05 |
Abatement Due Date |
2024-03-01 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2024-01-04 |
Nr Instances |
1 |
Nr Exposed |
3 |
Related Event Code (REC) |
Complaint |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.125(e)(4)(i): All vapor areas were not kept free of combustible debris and were not kept as free as practicable of combustible stock: Downstairs Dyeing Area: On, or about, October 16, 2023, an eight-gallon plastic storage container used as a dip tank to coat wooden parts with Dye #37 was supported by wooden pieces that appeared to be placed over cardboard that was coated with dye. Also, freshly dipped parts were stacked upon each other to dry and were stacked on what appeared to be cardboard coated with the dye. Dye #37 is a Category 2 flammable liquid with a flashpoint of -4�, F. |
|
Citation ID |
01003E |
Citaton Type |
Serious |
Standard Cited |
19100125 E05 |
Issuance Date |
2023-12-05 |
Abatement Due Date |
2024-03-01 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2024-01-04 |
Nr Instances |
1 |
Nr Exposed |
3 |
Related Event Code (REC) |
Complaint |
Gravity |
1 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.125(e)(5): A readily visible "No Smoking" sign was not posted near each dip tank: Downstairs Dyeing Area: On, or about, October 16, 2023, a "NO SMOKING" sign had not been posted where Dye #37, a Category 2 flammable liquid with a flashpoint of -4�, F was used to coat parts. |
|
Citation ID |
01004 |
Citaton Type |
Serious |
Standard Cited |
19100212 A01 |
Issuance Date |
2023-12-05 |
Abatement Due Date |
2024-01-24 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2024-01-04 |
Nr Instances |
2 |
Nr Exposed |
1 |
Related Event Code (REC) |
Complaint |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.212(a)(1): Machine guarding was not provided to protect operator(s) and other employees from hazard(s) created by in-running nip points: Upstairs Production Area: On, or about, October 16, 2023, in-running nip points created by the grinding belt or the grinding belt and rotary platen attachment belt running over pulleys were not provided with safeguarding on two Beaumont Metal Works model KMG J grinders. |
|
Citation ID |
01005 |
Citaton Type |
Serious |
Standard Cited |
19100219 E01 I |
Issuance Date |
2023-12-05 |
Abatement Due Date |
2024-01-24 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2024-01-04 |
Nr Instances |
2 |
Nr Exposed |
1 |
Related Event Code (REC) |
Complaint |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.219(e)(1)(i): Horizontal belts which had both runs 42 inches or less from the floor level were not fully enclosed by guards conforming to requirements specified in 29 CFR 1910.219(m) and (o): Upstairs Production Area: On, or about, October 16, 2023, the drive belts provided on two Beaumont Metal Works model KMG J grinders were not provided with a guard. The grinders were mounted on a counter top. |
|
Citation ID |
01006A |
Citaton Type |
Serious |
Standard Cited |
19101200 E01 |
Issuance Date |
2023-12-05 |
Abatement Due Date |
2024-03-01 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2024-01-04 |
Nr Instances |
1 |
Nr Exposed |
4 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.1200(e)(1): The employer did not develop, implement, and/or maintain at the workplace a written hazard communication program which describes how the criteria specified in 29 CFR 1910.1200(f), (g), and (h) will be met: Company: On, or about, October 16, 2023, the employer had not developed and implemented a written hazard communication program. Flammable liquids were used in the production areas. |
|
Citation ID |
01006B |
Citaton Type |
Serious |
Standard Cited |
19101200 F06 II |
Issuance Date |
2023-12-05 |
Abatement Due Date |
2024-01-24 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2024-01-04 |
Nr Instances |
1 |
Nr Exposed |
3 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.1200(f)(6)(ii): Except as provided in 29 CFR 1910.1200(f)(7) and 29 CFR 1910.1200(f)(8), the employer did not ensure that each container of hazardous chemicals in the workplace was labeled, tagged or marked with the product identifier and words, pictures, symbols, or combination thereof, which provide at least general information regarding the hazards of the chemicals and which, in conjunction with the other information immediately available to employees under the hazard communication program, would provide employees with the specific information regarding the physical and health hazards of the hazardous chemical: Basement Production Area: On, or about, October 16, 2023, a plastic container the contained Reagent Alcohol 200 proof, a Category 2 flammable liquid with a flashpoint of 33.2�, F was used to dispense the ethanol into the Datron M35 CNC milling machine. The container was not labeled with the identity of the contents and the hazard warnings associated with Reagent Alcohol. |
|
Citation ID |
01006C |
Citaton Type |
Serious |
Standard Cited |
19101200 G08 |
Issuance Date |
2023-12-05 |
Abatement Due Date |
2024-03-01 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2024-01-04 |
Nr Instances |
2 |
Nr Exposed |
4 |
Gravity |
1 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.1200(g)(8): The employer did not maintain in the workplace copies of the required safety data sheets for each hazardous chemical: Company: On, or about, October 16, 2023, the employer did not have and make available to employees copies of Safety Data Sheets for hazardous materials used in the work area including, but not limited to, Dye #37 and Reagent Alcohol, 200 proof, both Category 2 flammable liquids. |
|
Citation ID |
01006D |
Citaton Type |
Serious |
Standard Cited |
19101200 H01 |
Issuance Date |
2023-12-05 |
Abatement Due Date |
2024-03-01 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2024-01-04 |
Nr Instances |
1 |
Nr Exposed |
4 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.1200(h)(1): Employees were not provided effective information and training on hazardous chemicals in their work area at the time of their initial assignment and whenever a new hazard that the employees had not been previously trained about was introduced into their work area: Company: On, or about, October 16, 2023, the employer had not provided information and training to employees regarding the Hazard Communication Standard and hazards associated with hazardous chemicals used in the work area including, but not limited to, Dye #37 and Reagent Alcohol 200 proof, both Category 2 flammable liquids. |
|
|